Toshiba RAV-SM1101BT-E User Manual

Page 6

Advertising
background image

4

Model name

Appearance

Power supply

Type

Compressor

Motor

(kW)

Pole

Refrigerant charged

(kg)

Refrigerant control

Standard length

Max. total length

(m)

Pipe

Over 20m

Height difference

Outdoor lower

(m)

Outdoor higher

(m)

Outer

Height

(mm)

Width

(mm)

dimension

Depth

(mm)

Total weight

(kg)

Heat exchanger

Fan

Fan unit

Standard air flow High

(m³/h)

Motor

(W)

Connecting

Gas side

(mm)

pipe

Liquid side

(mm)

Protection device

Sound level

High (Mid./Low)

(dB•A)

(Note 2)

(Cooling/Heating)

RAV-SM1100AT-E

RAV-SM1400AT-E

Silky shade (Muncel 1Y8.5/0.5)

1 phase 230V (220 – 240V) 50Hz

(Power exclusive to outdoor is required.)

Hermetic compressor

2.0

3.75

8 poles

R410A 2.1

R410A 2.3

Pulse motor valve

20 (without additional charge)

50

Add 40g/m (Max. 1200g)

15

30

1340

900

320

75

85

Finned tube

2 Propeller fans

6800

7500

63 + 43

63 + 63

Ш15.9 (5/8”)

Ш9.5 (3/8”)

Discharge temp. sensor

Over-current sensor

Compressor thermo.

53/54

53/54

Note 1 : The cooling capacities and electrical characteristics are measured under the conditions specified by JIS B 8616 based

on the reference piping 7.5m.

Note 2 : The sound level is measured in an anechoic chamber in accordance with JIS B8616. Normally, the values measured in

the actual operating environment become larger than the indicated values due to the effects of external sound.

Note

: Rated conditions

Cooling : Indoor air temperature 27°C DB/19°C WB, Outdoor air temperature 35°C DB
Heating : Indoor air temperature 20°C DB, Outdoor air temperature 7°C DB/6°C WB