3. tools, X¡ ¡ x ¡ x – Toshiba RAV-SM1101BT-E User Manual

Page 29

Advertising
background image

27

7-3. Tools

7-3-1. Required Tools

The service port diameter of packed valve of the outdoor unit in the air conditioner using R410A is changed to
prevent mixing of other refrigerant. To reinforce the pressure-resisting strength, flare processing dimensions and
opposite side dimension of flare nut (For Ø12.7 copper pipe) of the refrigerant piping are lengthened.

The used refrigerating oil is changed, and mixing of oil may cause a trouble such as generation of sludge,
clogging of capillary, etc. Accordingly, the tools to be used are classified into the following three types.

(1) Tools exclusive for R410A (Those which cannot be used for conventional refrigerant (R22))

(2) Tools exclusive for R410A, but can be also used for conventional refrigerant (R22)

(3) Tools commonly used for R410A and for conventional refrigerant (R22)

The table below shows the tools exclusive for R410A and their interchangeability.

Tools exclusive for R410A (The following tools for R410A are required.)

Tools whose specifications are changed for R410A and their interchangeability

No.

Used tool



Flare tool

Copper pipe gauge for

‚

adjusting projection
margin

ƒ

Torque wrench

„

Gauge manifold

…

Charge hose

†

Vacuum pump adapter

‡

Electronic balance for
refrigerant charging

ˆ

Refrigerant cylinder

‰

Leakage detector

Š

Charging cylinder

Usage

Pipe flaring

Flaring by conventional
flare tool

Connection of flare nut

Evacuating, refrigerant
charge, run check, etc.

Vacuum evacuating

Refrigerant charge

Refrigerant charge

Gas leakage check

Refrigerant charge

R410A

air conditioner installation

Existence of

Whether conven-

new equipment

tional equipment

for R410A

can be used

Yes

*

(Note 1)

Yes

*

(Note 1)

Yes

X

Yes

X

Yes

X

Yes

X

Yes

X

Yes

X

(Note 2)

X

Conventional air

conditioner installation

Whether new equipment
can be used with
conventional refrigerant

¡

*

(Note 1)

X

X

¡
¡

X

¡

X

(Note 1) When flaring is carried out for R410A using the conventional flare tools, adjustment of projection

margin is necessary. For this adjustment, a copper pipe gauge, etc. are necessary.

(Note 2) Charging cylinder for R410A is being currently developed.

General tools (Conventional tools can be used.)

In addition to the above exclusive tools, the following equipments which serve also for R22 are necessary
as the general tools.

(1) Vacuum pump

Use vacuum pump by
attaching vacuum pump adapter.

(2) Torque wrench

(3) Pipe cutter

(4) Reamer

(5) Pipe bender

(6) Level vial

(7) Screwdriver (+, –)

(8) Spanner or Monkey wrench

(9) Hole core drill (Ø65)

(10) Hexagon wrench

(Opposite side 4mm)

(11) Tape measure

(12) Metal saw

Also prepare the following equipments for other installation method and run check.

(1) Clamp meter

(2) Thermometer

(3) Insulation resistance tester

(4) Electroscope

Advertising
This manual is related to the following products: