Toshiba RAV-SM1101BT-E User Manual

Page 79

Advertising
background image

77

UNIT

SET

CL

UNIT No.

SET DATA

R.C.

No.

4

2

1 2 3 4

3

1

<Operation procedure>

Returned to usual display

12-1-4. Monitor Function of Remote Controller Switch

n

Call of sensor temperature display

<Contents>

Each sensor temperature of the remote controller,
indoor unit, and outdoor unit can become known by
calling the service monitor mode from the remote
controller.

<Procedure>

1

Push

+

buttons simultaneously for 4

seconds or more to call the service monitor
mode.

The service monitor goes on, the master indoor
unit No. is displayed, and then temperature of the
item code

00

is displayed.

2

Push the temperature setup

/

buttons to select the sensor No. (Item code)
of the sensor to be monitored.

The sensor numbers are described below:

*1 Only master unit in group control

3

The temperature of indoor units and outdoor unit in a group control can be monitored by pushing

button to select the indoor unit to be monitored.

4

Pushing

button returns the display to usual display.

Indoor
unit data

Item code

00

01

02

03

04

Data name

Room temp (under control) *1

Room temp (remote controller)

Indoor suction temp

Indoor coil temp (TCJ)

Indoor coil temp (TC)

Outdoor
unit data

Item code

60

61

62

63

64

65

Data name

Heat exchanger temp TE

Outside temp TO

Discharge temp TD

Suction temp TS

Heat sink temp THS