Toshiba RAV-SM1101BT-E User Manual

Page 56

Advertising
background image

54

Check item code [14].

Correct inter-unit cable.

Correct connection of connector.

Correct connection of connector.

Replace IPDU.

Replace IPDU.
Correct connection of connector.

Check/Correct charged
refrigerant amount.

For RAV-SM560AT-E,
main circuit on control
P.C. board

For RAV-SM560AT-E,
check case thermo.

Check indoor P.C. board
(MCC-1402 or MCC-1403).
Defect

Replace

Check CDB.
Defect

Replace

Does outdoor unit operate?

Is setup of group address correct?

Is case thermo (CN500) connected?

Does case thermo operate?

Are 1, 2, 3 inter-unit cables normal?

Are connections from connectors

of inter-terminal blocks (1, 2, 3)

of indoor/outdoor units normal?

Does voltage between

2 and 3 of inter-terminal blocks (1, 2, 3)

of indoor unit vary?*

Is DC280V applied between

terminals of electrolytic capacitor

of IPDU main circuit?

Check indoor P.C. board
(MCC-1402).
Defect

Replace

*

As shown in the following figure,
perform measurement within
20 seconds after power ON.

Is DC7V power supplied to CDB?

Are cablings between Pin 2 and Pin 5

of CN800 and between IPDU

and CDB normal?

Black

White

3

2

1

Inter-terminal block

S5277G

NO

NO

NO

NO

NO

NO

NO

NO

NO

YES

YES

YES

YES

YES

YES

YES

YES

YES

[E04 error]/[04 error]