Toshiba RAV-SM1101BT-E User Manual

Page 64

Advertising
background image

62

NO

NO

YES

NO

YES

YES

* For RAV-SM560AT-E, replace control P.C. board.

Are connections of

cable/connector normal?

Are cablings of power and

current sensor normal?

Is not winding shorted?

(Is resistance between windings 0.6 to 1.2 ?)

Is compressor normal?

Is not earthed?

Is not winding opened?

Compressor error

Replace

Compressor error

Replace

Compressor error

Replace

Check and correct circuit cables.

Check and correct circuit cabling
such as cabling to compressor.

Check IPDU P.C. board.
Defect

Replace

Check IPDU.
Defect

Replace

* For RAV-SM560AT-E, replace control P.C. board.

YES

YES

NO

NO

NO

YES

[P29 error]/[16 error]

[H03 error]/[17 error]

Advertising
This manual is related to the following products: