Setup of line address of outdoor unit,
indoor unit address, and group address

Completion of cabling work

Turn on power of outdoor unit.

Turn on power of outdoor unit.

Connect one remote controller with
one indoor unit (1 : 1) tentatively with
communication cable.

END

Turn on power of outdoor unit.

Set to all indoor units one by one.

Do you arbitrarily set the

indoor unit address?

Do you change setting after

automatic setting at the first time?

Is refrigerant line 1 line?

Is group control performed?

Setup of automatic
address finishes within
4 to 5 minutes.

After completion of address
setup, change is to arbitral
address/group manually.

(To AUTO address mode)

(MANUAL)

( ) ( )

YES

YES

YES

YES

NO

NO

NO

13. ADDRESS SETUP

13-1. Address Setup

<Address setup procedure>

When an outdoor unit and an indoor unit are connected, or when an outdoor unit is connected to each indoor
unit respectively in the group operation even if multiple refrigerant lines are provided, the automatic address
setup completes with power-ON of the outdoor unit. The operation of the remote controller is not accepted while
automatic address works. (Approx. 4 to 5 minutes)

• When the following addresses are not stored in the neutral memory (IC10) on the indoor P.C. board, a test run

operation cannot be performed. (Unfixed data at shipment from factory)

Line address

Indoor unit address

Group address

Item code

12

13

14

Data at shipment

0099

0099

0099

Setup data range

0001 (No. 1 unit) to 0030 (No. 30 unit)

0001 (No. 1 unit) to 0030 (No. 30 unit)
Max. value of indoor units in the identical refrigerant line (Double twin = 4)

0000 : Individual (Indoor units which are not controlled in a group)
0001 : Master unit (1 indoor unit in group control)
0002 : Sub unit (Indoor units other than master unit in group control)