Step 2: cabinet preparation – Thermador PRG30 User Manual

Page 6

Advertising
background image

English 4

Step 2: Cabinet Preparation

1. The range is a free standing unit. If the unit is to be

placed adjacent to cabinets, the clearances shown in

Figure

1 are required. The same clearances apply to

island installations, except for the overhead cabinets,

which must have a space wide enough to accept the

flared island hood, as indicated in Figure

1.

2. These ranges may be recessed into the cabinets

beyond the edge of the front face of the oven (See

Figure

2).

CAUTION:

In these installations, the door and cabinet can

cause a pinching hazard.

3. The gas and electrical supply should be within the zone

shown in Figure

3a.

Note:

The maximum depth of over head cabinets installed on

either side of the hood is 13" (330 mm).

A 40-inch minimum clearance is required between the top

of the cooking surface and the bottom of an unprotected

cabinet. A 30-inch clearance can be used when the bottom

of the wood or metal cabinet is protected by not less than

1/4 inch of a flame retardant material covered with not less

than No. 28 MSG sheet steel, 0.015 inch (0.4 mm) thick

stainless steel, 0.024 inch (0.6 mm) aluminum, or 0.020

inch (0.5 mm) thick copper. Flame retardant materials bear

the mark:

UNDERWRITERS LABORATORIES INC. CLASSIFIED

MINERAL AND FIBER BOARDS SURFACE BURNING

CHARACTERISTICS

Followed by the flame spread and smoke ratings. These

designations are shown as “FHC (FIame Spread/Smoke

Developed)”. Materials with “O” flame spread ratings are

flame retardant. Local codes may allow other flame spread

ratings.

4. Any openings in the wall behind the range and in the

floor under the range must be sealed.

5. When there is less than a 12" horizontal clearance

between combustible material and the back edge of

the range above the cooking surface, a Thermador

Low Back or Pot and Pan Shelf must be installed. (See
Figure

2). When clearance to combustible material

is over 12", a Thermador Flush Island Trim may be

used. Figure

2 indicates the space required for each

type of backguard.

6. Always keep appliance area clear and free from

combustible materials, gasoline and other flammable

vapors and liquids.

7. Do not obstruct the flow of combustion and ventilation

air to the unit.

8. A 5 inch minimum clearance is needed when the range

is installed beside a combustible side wall.

A

s defined in the “National Fuel Gas Code” (ANSI

Z223.1, NFPA 54 Current Edition).

Advertising
This manual is related to the following products: