Capacity calculation for each indoor unit, Operating temperature range, Rated conditions – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual

Page 24

Advertising
background image

24

Capacity correction for frosting on the outdoor heat exchanger (heating mode)

Correct the heating capacity when frost was found on the outdoor heat exchanger.
Heating capacity =

Capacity after correction of outdoor unit × correction value of capacity resulting from frost

(Capacity after correction of outdoor unit: Heating capacity calculated in the previous

section.)

Capacity correction for frosting on the outdoor heat exchanger

Capacity corr

ection value

Outdoor air wet bulb temperature (°C)

Capacity calculation for each indoor unit

Capacity for each indoor unit =

Capacity after correction of outdoor unit ×

Operating temperature range

In cooling mode

In heating mode

Required standard capacity of indoor unit
Total value of standard indoor unit capacity

Usable range

(in pull-down mode)

Usable range

(in warming-up mode)

Rated conditions

Cooling: Indoor air temperature 27°C db/19°C wb.
Outdoor air temperature 35°C db.
Heating: Indoor air temperature 20°C db.
Outdoor air temperature 7°C db/6°C wb.

Outdoor air dry bulb temperatur

e (°C)

Indoor air wet bulb temperature (°C)

Continuous

operating

range

Outdoor air wet bulb temperatur

e (°C)

Indoor air dry bulb temperature (°C)

Continuous

operating

range

The unit can be operated even if outdoor
temperature falls to -20°C. However, the warranty
only covers operation down to -15°C, as lower
temperatures are outside the operating range.

When the outdoor air temperature falls to below
-15°C, unit operation may reduce the product life.