Outdoor units (combination) – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual

Page 62

Advertising
background image

62

Outdoor units (combination)

Rating

hp

26

28

30

Cooling only system MMY

AP2601T8

AP2801T8

AP3001T8

Heat pump system MMY

AP2601HT8

AP2801HT8

AP3001HT8

Outdoor unit type

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Inverter

Outdoor unit combination
cooling only MMY-MAP

1001T8 0801T8

0801T8

1001T8

1001T8

0801T8

1001T8

1001T8

1001T8

Outdoor unit combination
heat pump MMY-MAP

1001HT8 0801HT8 0801HT8 1001HT8 1001HT8 0801HT8 1001HT8 1001HT8 1001HT8

Cooling capacity

kW

73.0

78.5

84.0

Heating capacity

kW

81.5

88.0

95.0

Power supply ± 10%

V-ph-Hz

400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50 400-3-50

400-3-50

Voltage range

V

380-415 380-415 380-415 380-415

380-415

380-415

380-415

380-415

380-415

Power input, cooling

kW

20.29

22.27

24.26

Power factor, cooling

%

96

96

96

Operating current, cooling

A

30.51

33.48

36.48

EER, cooling

kW/kW

3.60

3.52

3.46

Starting current

A

1.0

1.0

1.0

Power input, heating

kW

20.51

22.60

24.82

Power factor, heating

%

95

96

97

Operating current, heating

A

31.16

33.98

36.93

COP, heating

kW/kW

3.97

3.89

3.83

Starting current

A

1.0

1.0

1.0

Unit appearance

Silky shade (Munsell 1Y8.5/0.5)

Dimensions
Height

mm

1800

1800

1800

1800

1800

1800

1800

1800

1800

Width

mm

990

990

990

990

990

990

990

990

990

Depth

mm

750

750

750

750

750

750

750

750

750

Total weight - cooling only unit

kg

256

256

256

256

256

256

256

256

256

Total weight - heat pump unit

kg

258

258

258

258

258

258

258

258

258

Heat exchanger

Finned type

Sound power level

dB(A)

75.0

75.5

76.0

Sound pressure level

dB(A) at 1 m 62.0

62.5

63.0

Fan type

Propeller Propeller Propeller Propeller

Propeller Propeller

Propeller

Propeller

Propeller

Motor power input

kW

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

0.6

Air flow

l/s

2917

2750

2750

2917

2917

2750

2917

2917

2917

m

3

/h

10500

9900

9900

10500

10500

9900

10500

10500

10500

Compressor type

Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic Hermetic

Hermetic

Motor power input

kW

3.1 x 2

2.3 x 2

2.3 x 2

3.1 x 2

3.1 x 2

2.3 x 2

3.1 x 2

3.1 x 2

3.1 x 2

Refrigerant charge R-410A*
Cooling

kg

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

11.0

Heating

kg

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

12.5

Pipework**
Suction line type - diameter

in

Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8 Brazed - 7/8

Liquid line type - diameter

in

Flare - 1/2 Flare - 1/2 Flare - 1/2 Flare - 1/2

Flare - 1/2

Flare - 1/2

Flare - 1/2

Flare - 1/2

Flare - 1/2

Balance pipe type - diameter

in

Flare - 3/8 Flare - 3/8 Flare - 3/8 Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Flare - 3/8

Maximum equivalent length separation

m

175

175

175

175

175

175

175

175

175

Maximum actual piping length

m

150 (if equivalent bend length is longer, equivalent length is standard)

Maximum total piping length

m

300

300

300

300

300

300

300

300

300

Maximum lift - indoor unit above/below***

m

40/50

40/50

40/50

40/50

40/50

40/50

40/50

40/50

40/50

Control wiring

Shielded wire 1.25 mm

2

x 2 cores up to 2000 m

Central remote controller

Shielded wire 1.25 mm

2

x 2 pieces up to 1000 m, 2.0 mm

2

x 2 pieces up to 2000 m

Max. number of connectable indoor units

43

47

48

High-pressure switch

MPa

Off: 2.90/On: 3.73

Protection devices

Discharge temperature sensor, suction temperature sensor, compressor crankcase heater,

high-pressure switch, overcurrent sensor, high-pressure sensor, low-pressure sensor,

overcurrent relay

Operating range, cooling†

°C

-5 to 43 db

-5 to 43 db

-5 to 43 db

Operating range, heating†

°C

-20 to 16 wb

-20 to 16 wb

-20 to 16 wb

Rated conditions:

Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

The standard piping equals 5 m main pipe length plus 2.5 m branch pipe length.

*

The amount does not cover extra piping lengths. Refrigerant must be added on-site in accordance with the actual piping length.

**

The maximum total piping length is the sum of one-way piping lengths on the liquid side or gas side.

***

If the indoor unit is above, maximum lift is reduced to 30 m, if the height difference between indoor units exceeds 3 m.

Please refer to page 24.

Advertising