Control wiring diagram – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual

Page 36

Advertising
background image

36

6. Control wiring diagram

1. All control wiring is 2-core non-polarity wire.
2. Be sure to use shielded wire for the following wiring to prevent noise disturbance.

Outdoor-outdoor/indoor-indoor/outdoor-indoor control wiring, central control wiring.

Table 1

Control wiring between indoor and outdoor units (L1, L2, L3)

Central control wiring (L4)

Wiring

2-core, non-polarity

Type

Shielded wire

Size

1.25 mm²: Up to 1000 m

Length

2.0 mm²: Up to 2000 m (*1)


(*1): Total of control wiring length for all refrigerant circuits ( L1 + L2 + L3 + L4 )

Table 2

Control wiring between outdoor units (L5)

Wiring

2-core, non-polarity

Type

Shielded wire

Size

1.25 mm² to 2.0 mm²

Length

Up to 100 m (L5)

Table 3

Remote controller wiring (L6, L7)

Wire

2-core

Size

0.5 mm² to 2.0 mm²

Length

Up to 500 m ( L6 + L7 ).

Up 400 m in case of wireless remote controller in group control.

Up to 200 m total length of control wiring between indoor units ( L6 ).

Central control

device

Super Modular Multi System

Table 1

Outdoor unit

Indoor unit

Master
unit

Master
unit

Master
unit

Slave
unit

Slave
unit

Slave
unit

Slave
unit

Table 1

Table 2

Table 3

Remote

controller

Remote controller

Remote controller

Advertising