3. Allowable length/height difference of refrigerant piping

Note: In case of connecting method in Example 2, a large amount of
refrigerant and refrigerant oil may return to the master unit. Therefore,
set the T-shape joint so that oil does not enter directly.

System restrictions

Max. No. of combined outdoor units

4 units

Max. capacity of combined outdoor units

48 hp

Max. No. of connected indoor units

48 units

Max. capacity of combined

H

2

≤ 15

135%

indoor units

H

2

> 15

105%

Note 1:

Combination of outdoor units: Master unit (1 unit) + slave units (0 to 3 units).

Master unit is the outdoor unit nearest to the connected indoor units.

Note 2:

Install the outdoor units in order of capacity.

(Master unit ≥ slave unit 1 ≥ slave unit 2 ≥ slave unit 3)

Note 3:

Refer to outdoor unit combination table on page 7.

Note 4:

Piping to indoor units shall be perpendicular to piping to the master outdoor unit as in
Example 1. Do not connect piping to indoor uints in the same direction as the master
outdoor unit in Example 2.

Allowable length and height difference of refrigerant piping

Allowable value Piping section

Piping length

Total extension of pipe (liquid pipe, actual length)

300 m

LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4+

L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j

Farthest piping length L (*)

Actual length

150 m

LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j

Equivalent length

175 m

Equivalent length of farthest piping from 1st branching Li (*)

65 m

L3 + L4 + L5 + L6 + j

Equivalent length of farthest piping between outdoor units LO (*)

25 m

LA + LB + Ld, (LA + Lb, LA + LB + Lc)

Max. equivalent length of main piping (***)

85 m

L1

Max. equivalent length of outdoor unit connection piping

10 m

Ld, (La, Lb, Lc)

Max. actual length of indoor unit connection piping

30 m

a, b, c, d, e, f, g, h, i, j

Height difference Height between indoor

Upper outdoor unit

50 m

——

and outdoor units H1

Lower outdoor unit

40 m (**)

——

Height between indoor units H2

30 m

——

Height between outdoor units H3

5 m

——

*

(D) is outdoor unit farthest from 1st branching, and ( j ) is indoor unit farthest from 1st branching.

**

If the height difference (H2) between indoor units exceeds 3 m, set below 30 m.

***

If the maximum combination capacity of the outdoor units is 46 hp or more, the maximum equivalent length is restricted up to 70 m.

D slave

unit 3

Slave
unit 1

Slave
unit 2

Slave
unit 1

Slave
unit 2

C slave

unit 2

B slave

unit 1

A master

unit

Master

unit

Master

unit

Connecting
piping of
outdoor unit

Outdoor unit

Height difference
between outdoor
units H3 ≤ 5 m

Height difference
betweeen outdoor
units H1 ≤ 50 m

T-shape branching
joint

Main
piping

Main connecting piping between outdoor units
Length corresponding to farthest piping
between outdoor units LO ≤ 25 m

Branching piping L2

1st branching
section

Branching

header

Connecting piping of indoor unit

Indoor unit

Equivalent length corresponding to farthest piping L ≤ 175 m

Equivalent length corresponding to farthest piping after 1st branching Li ≤ 65 m

Indoor unit

Height difference
between indoor
units H2 ≤ 30 m

Example 1

Example 2

Y-joint

La

Lb

Lc

LA

LB

Ld

L1

L3

L4

L6

L5