Indoor units

High-wall units (2 Series)

Model MMK-AP

0072H

0092H

0122H

Cooling capacity*

kW

2,2

2,8

3,6

Heating capacity

kW

2,5

3,2

4,0

Electrical data
Power supply

V-ph-Hz

230-1-50 (voltage range 220-240 V) - power supply to indoor unit only

Operating current

A

0,17

0,18

0,19

Power input

kW

0,017

0,018

0,019

Starting current

A

0,22

0,23

0,24

Unit appearance
Suction grille and side panel

Moon white

Discharge grille

Moon white

Bottom surface

Moon white

Unit dimensions
Height

mm

275

275

275

Width

mm

790

790

790

Depth

mm

208

208

208

Unit weight

kg

11

11

11

Heat exchanger

Finned tube

Sound proofing/heat insulating material

Non-flammable insulation

Fan type

Tangential fan

Fan motor power input

W

30

30

30

Air flow
High

l/s

133

142

150

Medium

l/s

117

125

125

Low

l/s

100

100

100

Air flow
High

m

3

/h

480

510

540

Medium

m

3

/h

420

450

450

Low

m

3

/h

360

360

360

Sound power level (high/medium/low)

dB(A)

48/45/42

49/46/42

50/46/42

Sound pressure level (high/medium/low)**

dB(A)

35/32/29

36/33/29

37/33/29

Air filter

Standard single filter supplied

Controller

Remote controller

Connection pipes
Gas connection diameter

in

3/8

3/8

3/8

Liquid connection diameter

in

1/4

1/4

1/4

Drain connection, nom. dia (polyvinyl tube)

mm

16

16

16

Rated conditions:

Cooling: Indoor air temperature 27°C db/19°C wb, outdoor air temperature 35°C db

Heating: Indoor air temperature 20°C db, outdoor air temperature 7°C db/6°C wb

*

Cooling capacities and electrical data are measured at the conditions specified by JIS B 8615, based on the reference piping which consists of 5 m of main
piping and 2.5 m of branch piping connected with 0 metre height.

**

The sound pressure level is measured in an anechoic chamber in accordance with JIS B 8616. Normally the values measured in the actual operating
environment become larger than the indicated values due to the effects of external sound.