Selection of refrigerant piping – Toshiba SUPER MODULAR MULTI HFC R-410A User Manual

Page 32

Advertising
background image

32

4. Selection of refrigerant piping

Pipe size of outdoor unit (Table 1)

Model name

MMY-

Gas side

Liquid side

MAP0501T8

MAP0501HT8

Ш5/8”

Ш3/8”

MAP0601T8

MAP0601HT8

Ш3/4”

Ш3/8”

MAP0801T8

MAP0801HT8

Ш7/8”

Ш1/2”

MAP1001T8

MAP1001HT8

Ш7/8”

Ш1/2”

MAP1201T8

MAP1201HT8

Ш1-1/8”

Ш1/2”

Connecting pipe size between outdoor units (Table 2)

Total capacity code of

Gas side

Liquid side

Balance pipe

outdoor units downstream
14 to below 22

Ш1-1/8”

Ш5/8”

Ш3/8”

22 to below 26

Ш1-3/8”

Ш5/8”

Ш3/8”

26 to below 36

Ш1-3/8”

Ш3/4”

Ш3/8”

36 or more

Ш1-5/8”

Ш7/8”

Ш3/8”

Size of main pipe (Table 3)

Total capacity code of

Gas side

Liquid side

all outdoor units (*1)
Below 6

Ш5/8”

Ш3/8”

6 to below 8

Ш3/4”

Ш3/8”

8 to below 12

Ш7/8”

Ш1/2”

12 to below 14

Ш1-1/8”

Ш1/2”

14 to below 22

Ш1-1/8”

Ш5/8”

22 to below 26

Ш1-3/8”

Ш5/8”

26 to below 36

Ш1-3/8”

Ш3/4”

36 to below 46

Ш1-5/8”

Ш7/8”

46 or more

Ш1-5/8” (*5)

Ш7/8”

Determine thickness of the main pipe according to capacity of the outdoor units.

Pipe size between branching sections (Table 4)

Total capacity code of

Gas side

Liquid side

indoor units downstream (*1)
2.8 or less

Ш1/2”

Ш3/8”

2.8 to below 6.4

Ш5/8”

Ш3/8”

6.4 to below 12.2

Ш7/8”

Ш1/2”

12.2 to below 20.2

Ш1-1/8”

Ш5/8”

20.2 to below 25.2

Ш1-3/8”

Ш5/8”

25.2 to below 35.2

Ш1-3/8”

Ш3/4”

35.2 or more

Ш1-5/8”

Ш7/8”

If the total capacity code value of indoor units exceeds that of the outdoor units,
apply the capacity code of the outdoor units.

Piping of indoor unit (Table 5)

Indoor unit size

Gas side

Liquid side

007 to 012

Actual length 15 m or less Ш3/8”

Ш1/4”

Actual length exceeds 15 m Ш1/2”

Ш1/4”

015 to 018

Ш1/2”

Ш1/4”

024 to 056

Ш5/8”

Ш3/8”

072 to 096

Ш7/8”

Ш1/2”

Selection of branching section (Table 6)

Total capacity code of indoor unit (*1)

Model

Y-shape

Below 6.4

RBM-BY53E

branching joint

6.4 to below 14.2

RBM-BY103E

(*2)

14.2 to below 25.2

RBM-BY203E

25.2 or more

RBM-BY303E

Branching

For 4

Below 14.2

RBM-HY1043E

header

branching 14.2 to below 25.2

RBM-HY2043E

(*3)

For 8

Below 14.2

RBM-HY1083E

branching 14.2 to below 25.2

RBM-HY2083E

T-shape

1 set of 3 types of T-shape joint pipes as

RBM-BT13E

branching joint described below:
(For connecting The required quantity is arranged and
outdoor unit)

combined at the site.

• Balance pipe (Corresponding difference

Ш3/8”) Ч 1

• Piping at liquid side (Corresponding

difference Ø3/8” to Ш7/8”) Ч 1

• Piping at gas side (Corresponding

difference Ø5/8” to Ш1-5/8”) Ч 1

Minimum wall thickness for R-410A application (Table 7)

Soft

Half hard or hard

OD (Inch)

Minimum wall thickness (mm)

OK

OK

1/4”

0.80

OK

OK

3/8”

0.80

OK

OK

1/2”

0.80

OK

OK

5/8”

1.00

NG

OK (*4)

3/4”

1.00

NG

OK (*4)

7/8”

1.00

NG

OK (*4)

1-1/8”

1.00

NG

OK (*4)

1-3/8”

1.10

NG

OK (*4)

1-5/8”

1.25

*1

Code is determined according to the unit size. For details, refer to pages 7-9.

*2

When using Y-shape branching joint for 1st branching, select according to capacity code of outdoor unit.

*3

For one line after header branching, indoor units with a maximum of 6.0 capacity code in total can be connected.

*4 If the pipe size is Ø3/4” or more, use a hard type or half hard type for material of the pipe.
*5

The maximum equivalent length of the main pipe should be 70 m or shorter.

Slave
unit 3

Slave
unit 2

Slave
unit 1

Master

unit

Outdoor unit

Balance pipe

T-shape
branching joint

Main piping

Outdoor unit
connection
piping

Main connection
piping between
outdoor units

1st branching
section

Indoor unit
connection piping

Indoor unit

Y-shape
branching
joint

Indoor unit connection piping

Header branching pipe

Indoor unit

Branching pipe