White Rodgers 1F92W-51 User Manual

Page 32

Advertising
background image

32

cycles are too long, press

TIME

BACK

to decrease

the cycle time. To set COOL anticipation, press

SET

CLOCK

and

SET

DAY

at the same time again. The

display will show COOL 14 (factory
preprogrammed cooling anticipation). Use

TIME

FWD

and

TIME

BACK

to adjust anticipation. To set

AUXILIARY heat anticipation (not applicable to

multi-stage use), press

SET

CLOCK

and

SET

DAY

at the

same time again. The display will show AUX 8
(factory preprogrammed auxiliary anticipation).

Use

TIME

FWD

and

TIME

BACK

to adjust anticipation.

Press

RUN

PRGM

to return to your program.

LOW BATTERY INDICATOR — The word BAT
will flash on the display if the battery is low and
should be replaced. When BAT is displayed

continuously (non-flashing), 24 VAC power is
not being supplied and the thermostat is work-
ing on battery power only.

COMPRESSOR SHORT CYCLE PROTEC-
TION
— To protect your compressor from poten-
tial damage due to rapid cycling, this thermostat
has a built-in delay of 5 minutes between cooling
cycles. The following may cause a time delay in
COOL or HEAT:

a) Return of power after a momentary power

outage.

b) Pressing

SYSTEM

HEAT-OFF-COOL-AUTO

to change operating

modes.

c) Pressing

or

to create a call for

COOL or HEAT too soon after a previous
call.

During lockout in the COOL mode, the blower
will operate, but compressor operation will be
delayed.