6-8

NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide

To enable the Automated Mode, access the General Parameters menu (see

Section 5.3.1) and then set the "Automated Mode" option to the "On" state.

When the Automated Mode is enabled, NBB functions will change

as follows:

1. All Password Security Suppressed: When a user attempts to access

the command mode, the password prompt will not be displayed at either

the Console Port or Network Port. Unless specifically restricted by the

IP Security Function, all users will be allowed to access both switching

and configuration functions, and all commands will be immediately

accepted without the requirement to enter a password.

2. Status Screen Suppressed: The status screens will not be

automatically displayed after commands are successfully executed.

Note however, that the /S command can still be invoked to display the

status screen if needed.

3. "Sure?" Prompt Suppressed: All commands are executed without

prompting for user confirmation.

4. Error Messages Suppressed: If the [Enter] key is pressed without

entering a command, the NBB will not respond with the "Invalid

Command" message. Note however, that an error message will still be

generated if commands are invoked using invalid formats or arguments.

All other status display and configuration commands will still function

as normal.

6.5. Manual Operation

In addition to the command driven functions available via the Web Browser

Interface and Text Interface, the NBB’s switched plugs can also be toggled

On and Off manually. To manually toggle plugs On or Off, press the Manual

Control Button, and hold it down for approximately three seconds.
If desired, the Manual Switch Button Option (accessed via the General

Parameters Menu), can be used to completely disable the manual power button

as described in Section 5.3.1.
For more information on the Manual Switch Button Parameter, please refer to

Section 5.3.1.

Note:

When the Manual Switch Button is used, Boot / Sequence

Delay Times will be applied.