B. specifications – Western Telematic NBB-1600-D20 User Manual

Page 58

Advertising
background image

Apx-2

NBB-1600-D20/D16 Series: Network Boot Bars - User's Guide

B. Specifications

Power Input / Output ; Model NBB-1600-D20 (120 VAC)

AC Input: Two Separate Circuits; 20 Amps Max. per Circuit (40 Amps Total)

Voltage: 100 - 120 VAC 60 Hz

Connectors: Two (2) IEC320-C20 Inlets

AC Outputs: Sixteen (16) Plugs, Split into Two 20 Amp Circuits.

Connectors: Sixteen (16) NEMA 5-15R Outlets

Load:

Each Outlet: 15 Amps

Circuit "A" (Plugs 1 to 8): 20 Amps Total

Circuit "B" (Plugs 9 to 16): 20 Amps Total

Power Input / Output ; Model NBB-1600E-D20 (208 VAC)

AC Input: Two Separate Circuits; 20 Amps Max. per Circuit (40 Amps Total)

Voltage: 100 - 240 VAC 50/60 Hz

Connectors: Two (2) IEC320-C20 Inlets

AC Outputs: Sixteen (16) Plugs, Split into Two 20 Amp Circuits.

Connectors: Sixteen (16) IEC320-C13

Load:

Each Outlet: 15 Amps

Circuit "A" (Plugs 1 to 8): 20 Amps Total

Circuit "B" (Plugs 9 to 16): 20 Amps Total

Power Input / Output ; Model NBB-1600CE-D16 (230 VAC)

AC Input: Two Separate Circuits; 16 Amps Max. per Circuit (32 Amps Total)

Voltage: 100 - 240 VAC 50/60 Hz

Connectors: Two (2) IEC320-C20 Inlets

AC Outputs: Sixteen (16) Plugs, Split into Two 16 Amp Circuits.

Connectors: Sixteen (16) IEC320-C13

Load:

Each Outlet: 10 Amps

Circuit "A" (Plugs 1 to 8): 16 Amps Total

Circuit "B" (Plugs 9 to 16): 16 Amps Total

Console / Modem Port Interface:

Connector: DB9M, RS232C, DTE
Coding: Serial ASCII, 8 Bits, No Parity

Physical / Environmental:

Size:

Length: 43.75" (111.1 cm)

Depth: 3.00" (7.6 cm)

Width: 1.75" (4.5 cm)

Weight: 12 lbs. Shipping Weight

Temperature: (Operating) 32°F to 122°F (0°C to 50°C)
Humidity: 10 - 90% RH

Advertising