The ac bypass switch, Operating the ac bypass switch – Xantrex Technology ACCB-L User Manual

Page 54

Advertising
background image

Operation

3–2

973-0031-01-01 Rev A

The AC Bypass Switch

During normal operation (Figure 3-2 on page 3–3), AC power passes from the
single external AC source (generator or grid) through the inverter to the AC loads.
The inverter monitors the incoming power and uses this power to keep the
batteries charged.
When this external source of AC power is not available, the inverter switches to
external DC power (e.g., batteries, generator, solar, wind, hydro) and continues to
power the load.
When performing inverter maintenance, the breakers can be switched to the
Bypass Operation (Figure 3-3 on page 3–3) which allows the AC loads to be
powered directly from the external AC source without affecting connected AC
loads.
To de-energize both circuits, switch the breaker pair to the OFF position (Figure
3-4 on page 3–4).

Operating the AC Bypass Switch

Once the AC voltage has been applied, the bypass switch is ready for operation.
Under normal operation the Inverter Output breaker is ON.
There are three possible modes of operation for the bypass switch:

“Normal Operation”

“Bypass Operation”

“AC Input/Output Off”

Figure 3-1 AC Bypass Switch Mode Summary

AC OFF OPERATION:
Left Breaker = OFF
Right Breaker = OFF

Utility/Generator/Inverter AC
power disconnected to Inverter
AC Distribution Panel

NORMAL OPERATION:
Left Breaker = OFF
Right Breaker = ON

Inverter AC power
available to Inverter
AC Distribution Panel

BYPASS OPERATION:
Left Breaker = ON
Right Breaker = OFF

Utility or Generator AC
power available to Inverter
AC Distribution Panel

OFF

ON

60

60

OFF

ON

OFF

ON

60

60

OFF

ON

OFF

ON

60

60

OFF

ON

BOTH OFF TO DISCONNECT AC OUTPUT

INVERTER

Bypass 1

on to bypass

INVERTER

DISCONNECT 1

on for normal operation

BOTH OFF TO DISCONNECT AC OUTPUT

INVERTER

Bypass 1

on to bypass

INVERTER

DISCONNECT 1

on for normal operation

BOTH OFF TO DISCONNECT AC OUTPUT

INVERTER

Bypass 1

on to bypass

INVERTER

DISCONNECT 1

on for normal operation

Advertising
This manual is related to the following products: