PREINSTALLATION
XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE
3-19
50 Hz WYE printer outlet voltages
Note:
50 Hz WYE configurations only: Measure the WYE
connection voltages at the power source. Table 3-9 shows 415
voltages. Table 3-10 shows 380 and 400 voltages.
All power outlets must be dedicated only to this equipment. Ensure
that each power cord has a separate circuit.
Table 3-9.
Printer (50 Hz only) WYE connection for 415 V
Service outlet
Service outlet
configuration
Measurement
Nominal
Range
5 Wire 415 V
Line 1 to Line 2
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 2 to Line 3
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 1 to Line 3
415 V RMS
374-457 V RMS
5 Wire 415 V
Line 1 to Neutral
240 V RMS
216-264 V RMS
5 Wire 415 V
Line 2 to Neutral
240 V RMS
216-264 V RMS
5 Wire 415 V
Line 3 to Neutral
240 V RMS
216-264 V RMS
Table 3-10.
Printer (50 Hz only) WYE connection for 380 V and
400 V Service outlet
Service outlet
configuration
Measurement
Nominal
Range
5 Wire 380 V
Line 1 to Line 2
380 V RMS
342-419 V RMS
5 Wire 380 V
Line 2 to Line 3
380 V RMS
342-419 V RMS
5 Wire 380 V
Line 1 to Line 3
380 V RMS
342-419 V RMS
5 Wire 380 V
Line 1 to Neutral
220 V RMS
198-242 V RMS
5 Wire 380 V
Line 2 to Neutral
220 V RMS
198-242 V RMS
5 Wire 380 V
Line 3 to Neutral
220 V RMS
198-242 V RMS
5 Wire 400 V
Line 1 to line 2
400 V RMS
358-438 V RMS
5 Wire 400 V
Line 2 to line 3
400 V RMS
358-438 V RMS
5 Wire 400 V
Line 1 to Line 3
400 V RMS
358-438 V RMS
5 Wire 400 V
Line 1 to Neutral
230 V RMS
207-253 V RMS
5 Wire 400 V
Line 2 to Neutral
230 V RMS
207-253 V RMS
5 Wire 400 V
Line 3 to Neutral
230 V RMS
207-253 V RMS