PREINSTALLATION

XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE

3-19

50 Hz WYE printer outlet voltages

Note:

50 Hz WYE configurations only: Measure the WYE

connection voltages at the power source. Table 3-9 shows 415
voltages. Table 3-10 shows 380 and 400 voltages.

All power outlets must be dedicated only to this equipment. Ensure
that each power cord has a separate circuit.

Table 3-9.

Printer (50 Hz only) WYE connection for 415 V
Service outlet

Service outlet
configuration

Measurement

Nominal

Range

5 Wire 415 V

Line 1 to Line 2

415 V RMS

374-457 V RMS

5 Wire 415 V

Line 2 to Line 3

415 V RMS

374-457 V RMS

5 Wire 415 V

Line 1 to Line 3

415 V RMS

374-457 V RMS

5 Wire 415 V

Line 1 to Neutral

240 V RMS

216-264 V RMS

5 Wire 415 V

Line 2 to Neutral

240 V RMS

216-264 V RMS

5 Wire 415 V

Line 3 to Neutral

240 V RMS

216-264 V RMS

Table 3-10.

Printer (50 Hz only) WYE connection for 380 V and
400 V Service outlet

Service outlet
configuration

Measurement

Nominal

Range

5 Wire 380 V

Line 1 to Line 2

380 V RMS

342-419 V RMS

5 Wire 380 V

Line 2 to Line 3

380 V RMS

342-419 V RMS

5 Wire 380 V

Line 1 to Line 3

380 V RMS

342-419 V RMS

5 Wire 380 V

Line 1 to Neutral

220 V RMS

198-242 V RMS

5 Wire 380 V

Line 2 to Neutral

220 V RMS

198-242 V RMS

5 Wire 380 V

Line 3 to Neutral

220 V RMS

198-242 V RMS

5 Wire 400 V

Line 1 to line 2

400 V RMS

358-438 V RMS

5 Wire 400 V

Line 2 to line 3

400 V RMS

358-438 V RMS

5 Wire 400 V

Line 1 to Line 3

400 V RMS

358-438 V RMS

5 Wire 400 V

Line 1 to Neutral

230 V RMS

207-253 V RMS

5 Wire 400 V

Line 2 to Neutral

230 V RMS

207-253 V RMS

5 Wire 400 V

Line 3 to Neutral

230 V RMS

207-253 V RMS