PREINSTALLATION

XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE

3-21

50 Hz system controller and peripheral cabinet power cord configurations

Figure 3-11 shows the 50 Hz system controller power cord
configuration.

Figure 3-11. System controller and peripheral cabinet power

cord 50 Hz installation 200/230 VAC, single phase,
15A

Note:

The 50 Hz plug and receptacle specifications vary according

to local codes.

60 Hz printer outlet voltages

Note:

All power outlets must have a dedicated circuit for each

system equipment piece. Ensure that each power cord has a
separate circuit.

Refer to table 3-12 for the 60Hz voltage requirements at the power
outlet.

Table 3-12.

Printer (50 Hz) voltage requirements at power
outlet

Service outlet
configuration

Measurement

Nominal

Range

4 Wire

Line 1 to Neutral

120 V RMS

107-127 V RMS

4 Wire

Line 2 to Neutral

120 V RMS

107-127 V RMS

4 Wire

Neutral to
Ground

0 V RMS

0-10 V RMS

4 Wire

Line 1 to Line 2

208 V RMS

182-220 V RMS

Line 1 to Line 2

240 V RMS

210-254 V RMS