PREINSTALLATION

3-20

XEROX DOCUPRINT 96/DOCUPRINT 96MX LPS INSTALLATION PLANNING GUIDE

50 Hz DELTA printer outlet voltages

Note:

All power outlets must be dedicated only to this equipment.

Ensure that each power cord has a separate circuit.

50 Hz DELTA configurations only: Measure the DELTA connection
voltages at the power source. The required voltages are shown in
table 3-11.

Consult with your service representative to determine the type of plug
and receptacle to be used for your 50 Hz printer.

Table 3-11.

Printer (50 Hz only) DELTA connection for 220/230/
240 V Service outlet

Service outlet
configuration

Measurement

Nominal

Range

4 Wire 220 V

Line 1 to Line 2

220 V RMS

198-242 V RMS

4 Wire 220 V

Line 2 to Line 3

220 V RMS

198-242 V RMS

4 Wire 220 V

Line 1 to Line 3

220 V RMS

198-242 V RMS

4 Wire 230 V

Line 1 to line 2

230 V RMS

207-253 V RMS

4 Wire 230 V

Line 2 to line 3

230 V RMS

207-253 V RMS

4 Wire 230 V

Line 1 to line 3

230 V RMS

207-253 V RMS

4 Wire 240 V

Line 1 to Line 2

240 V RMS

216-264 V RMS

4 Wire 240 V

Line 2 to Line 3

240 V RMS

216-264 V RMS

4 Wire 240 V

Line 1 to Line 3

240 V RMS

216-264 V RMS