12. Inverted “T” Foundation 2.66" Outside Stiffened Commercial Tanks
PNEG-318 Concrete Foundation Recommendations for GSI Grain Bins
75
Diameter of Bin: 18'
Soil Bearing Capacity: 4000 PSF
Ring #
12
14
16
18
A
1'-0"
1'-0"
1'-0"
1'-0"
B
1'-4"
1'-7"
1'-11"
2'-4"
C
9'-10"
9'-10"
9'-10"
9'-10"
D
9'-10"
10'-0"
10'-1"
10'-4"
M
5 #4's
5 #4's
5 #4's
5 #4's
N
2 #5's
2 #5's
2 #5's
3 #5's
P
#5 @ 14" c/c
#5 @ 14" c/c
#5 @ 14" c/c
#5 @ 14" c/c
Rerod
#4 (ft.)
1700
1700
1700
1700
#5 (ft.)
300
300
300
300
#6 (ft.)
0
0
0
0
Cu. Yds.
Concrete
Footing
3
4
5
5
Wall
10
10
10
10
Floor
5
5
5
5
Total
18
19
20
20
Diameter of Bin: 21'
Soil Bearing Capacity: 4000 PSF
Ring #
12
14
16
18
A
1'-0"
1'-0"
1'-0"
1'-0"
B
1'-4"
1'-8"
2'-1"
2'-5"
C
11'-4"
11'-4"
11'-4"
11'-4"
D
11'-4"
11'-6"
11'-8"
11'-10"
M
5 #4's
5 #4's
5 #4's
5 #4's
N
2 #5's
2 #5's
2 #5's
3 #5's
P
#5 @ 14" c/c
#5 @ 14" c/c
#5 @ 14" c/c
#5 @ 14" c/c
Rerod
#4 (ft.)
2100
2100
2100
2100
#5 (ft.)
300
300
300
500
#6 (ft.)
0
0
0
0
Cu. Yds.
Concrete
Footing
4
5
6
6
Wall
12
12
12
12
Floor
6
6
6
6
Total
22
23
24
24