15. Inverted “T” Foundation 4" Outside Stiffened (WCL Series) Commercial Tanks

PNEG-318 Concrete Foundation Recommendations for GSI Grain Bins

99

Diameter of Bin: 24'
Soil Bearing Capacity: 3000 PSF

Ring #

12

14

16

18

A

1'-0"

1'-0"

1'-0"

1'-0"

B

3'-2"

3'-11"

4'-10"

5'-7"

C

12'-10"

12'-10"

12'-10"

12'-10"

D

13'-8"

14'-0"

14'-5"

14'-9"

M

5 #4's

5 #4's

5 #4's

5 #4's

N

3 #5's

3 #5's

5 #5's

4 #5's

P

#5 @ 14" c/c

#5 @ 14" c/c

#5 @ 14" c/c

#5 @ 11" c/c

Rerod

#4 (ft.)

2400

2400

2200

2200

#5 (ft.)

600

600

700

1000

#6 (ft.)

0

0

0

0

#7 (ft.)

0

0

0

0

Cu. Yds.

Concrete

Footing

9

11

14

16

Wall

15

15

15

15

Floor

8

8

8

8

Total

32

34

37

39

Diameter of Bin: 27'
Soil Bearing Capacity: 3000 PSF

Ring #

12

14

16

18

A

1'-0"

1'-0"

1'-0"

1'-0"

B

3'-4"

4'-3"

5'-1"

5'-10"

C

14'-4"

14'-4"

14'-4"

14'-4"

D

15'-3"

15'-8"

16'-0"

16'-4"

M

5 #4's

5 #4's

5 #4's

5 #4's

N

4 #5's

5 #5's

5 #5's

6 #5's

P

#5 @ 14" c/c

#5 @ 14" c/c

#5 @ 14" c/c

#6 @ 13" c/c

Rerod

#4 (ft.)

2700

2700

2700

2700

#5 (ft.)

700

700

900

600

#6 (ft.)

0

0

0

500

#7 (ft.)

0

0

0

0

Cu. Yds.

Concrete

Footing

11

14

16

19

Wall

16

16

16

16

Floor

10

10

10

10

Total

37

40

42

45