6. Vision Touch Screen Display

PNEG-1707 TM-Series Tower Dryer

31

1. Diagnostics: The Diagnostics operations are described in greater detail in the service

section

on Page 49

of this manual.

2. Differential: Touching the Differential button will display the Modify Burner Differential

Settings screen.

(See Figure 6K.)

Adjusting the burner differential settings allows the

operator to keep the plenum temperature within a certain range. For example: If you have
the temperature set point at 180° and you select ± 3° as the burner differential, then the
burner will switch to low heat at 183° and back to high heat at 177°. To modify a burner
differential setting first touch the Plenum button you wish to modify, then select one of the
five (5) differential setting button on the right side of the Modifying Burner Differential Settings
screen. Touch the Accept/Exit button to save settings and return to the Select Hardware
Setup Parameter to Modify screen. NOTE: Tower dryer only have plenum #1.

Figure 6K

3. Printer setup: This section only applies if the dryer is equipped with a printer.

Figure 6L