OSRAM QUICKTRONIC-M ECG for circular FL 16 mm User Manual
Page 75
74
QUICKTRONIC
®
30mm height
Max. number of ECGs
with automatic circuit
breakers
Ip[A]
T
H
[µs] 10A
16A
QT-FH 1x14-35 CW
20 210 17
28
QT-FH 2x14-35 CW
20 210 17
28
QT-FQ 1x24 CW
17 155 25
41
QT-FQ 1x39 CW
17 155 25
41
QT-FQ 1x49 CW
20 210 17
28
QT-FQ 1x54 CW
20 210 17
28
QT-FQ 1x80 CW
28 230 8
13
QT-FQ 2x24 CW
20 210 17
28
QT-FQ 2x39 CW
28 230 8
13
QT-FQ 2x49 CW
28 230 8
13
QT-FQ 2x54 CW
28 230 8
13
QT-FH 1x14
17 155 25
41
QT-FH 1x21
17 155 25
41
QT-FH 3x14 CW
20 230 17
28
QT-FH 4x14 CW
20 230 17
28
QUICKTRONIC
®
for FC
Max. number of ECGs
with automatic circuit
breakers
Ip[A]
T
H
[µs] 10A
16A
QT-FC 1x55/230-240 S
28 230 8
13
7.4 Lamp/ECG
Combinations
Valid Lamp-ECG combinations are available in the Lighting Programme.
Edition January 2005 also available in
Section 9 or under
www.osram.com/ecg
7.5 OSRAM
Installation
Tips for T5-Systems
Maximum lamp temperatures for T5/
∅ 16 mm fluorescent lamps compared
to T8/
∅ 26 mm-fluorescent lamps
Max. temp. at lamp caps
Lamp centre
Electrode area
°C
°C
°C
T8/L36W
120
45...55
100...120
T8/L58W
140
50...65
110...130
T5/FH28W
120
40...60
160 (200...250*)
T5/FQ54W
120
50...70
160 (200...250*)
*)
in
FH
-
E
C
G
-
Luminaires
the lamp could be incorrectly used,
e
.
g
. FH35W
with
FQ80W