To connect DC input power on DC models:
1. If you have not already done so, unpack the Regeneration Tap and verify

that you have appropriate DC power cables. You also need a Phillips

screwdriver to complete the installation.

2. If present, remove the protective covers from the DC power terminal

blocks.

3. Connect an earth ground lead to the terminal labeled with the ground symbol

( ), which is the left-most terminal, on both DC power terminal blocks on

the rear of the chassis. Use the screwdriver to tighten the connections. Also

connect the earth ground to the ground stud near the center of the rear panel.

4. Connect one of the DC power cables to one of the DC power terminal

blocks on the rear panel. Connect the negative (-48VDC) side of the cable

to the terminal labeled with the minus symbol (—) and the positive (0V)

side of the cable to the terminal labeled with the plus symbol (+). The

minus terminal is in the center and the plus terminal is on the right. Use

the screwdriver to tighten the connections.

5. Repeat Step 4 for the other DC power cable, connecting it to the remaining

DC power terminal block on the rear panel.

6. Carefully connect the other ends of the DC power cables to two -48VDC

power sources. If possible, turn off the power to the power source while

you are making these connections. Be sure to connect the positive sides

of the cables to the positive (plus) sides of the power sources, and the

negative sides of the power cables to the negative (minus) sides of the

power sources.

Installation in a Restricted Access Location in Finland
and Norway

Because of concerns about unreliable earthing in Finland and Norway,

this equipment must be installed in a Restricted Access Location (RAL) in

these countries. An RAL is defined as an access that can be gained only by

trained service personnel who have been instructed about the reasons for the

restricted access and any safety precautions that must be taken. In these cases,

the use of a tool (such as lock and key) or other means of security is required

for access to this equipment.