Level the base on a concrete foundation, Connect the optional storage tank – Xylem AquaBoost CS and VS Pumping Packages User Manual
Page 28
![background image](/manuals/310376/28/background.png)
Level the base on a concrete foundation
1. Place the pump package on its concrete foundation.
2. Place 1.00 in./(25.40 mm) thick steel shims or wedges on both sides of each anchor
bolt in order to support the pump package.
Make sure you also place the shims or wedges midway between the bolts.
This also provides a means of leveling the base.
Connect the optional storage tank
1. If the unit is a simplex configuration, then install the tank to the top connection of the
discharge cross as shown:
Constant speed
Variable speed
1
2
RS000019
1.
Storage tank
2.
Discharge gauge
1
2
RS000021
1.
Storage tank
2.
Discharge gauge
2. If the unit is a duplex configuration, then connect the tank to the discharge manifold as
shown:
Constant speed
Variable speed
1
2
RS000020
1.
Storage tank
2.
Discharge gauge
1
2
RS000022
1.
Storage tank
2.
Discharge gauge
Installation
26