When a low-suction or high-temperature thermal cutout situation occurs, the red light
indicator illuminates. An auto reset feature is provided in order to return the pumps to
operational state.

Variable speed operation

Variable speed simplex – for capacities up to 110 gpm

The pressure transducer monitors the system pressure and sends a feedback signal to the
controller. Depending upon the feedback, the controller then changes the speed of the
pump.

Condition

Description

The system pressure falls below the set point.

The pump starts automatically and pump speed

continues to ramp up until the system pressure satisfies

the set point.

The system pressure rises above the set point.

The pump automatically reduces speed until the system

pressure reaches the set point, provided the minimum

run timer has expired.

Variable speed duplex – for capacities up to 220 gpm

The pressure transducer monitors the system pressure and sends feedback signal to the
controller. Depending upon the feedback, the controller changes the speed of the pump
or stages/de-stages the other pump.

Condition

Description

The system pressure falls below the set point.

The pump starts automatically and pump speed

continues to ramp up until the system pressure satisfies

the set point.

The system pressure rises above the set point.

The pump automatically reduces speed until the system

pressure reaches the set point, provided the minimum

run timer has expired.

Low-suction pressure switch

Simplex and duplex units will run when there is demand unless the optional low-suction
pressure switch trips due to low city pressure.
The low-suction condition resets automatically when city pressure returns to an acceptable
level.

Temperature relief valve

The variable-speed units have a temperature relief valve that senses water temperature
inside the pump.
The valve opens and closes depending on the water temperature. This modulating action
maintains a relatively constant fluid temperature even as operating conditions vary.

Condition

Description

The water temperature exceeds the valve opening

temperature, typically 120ºF (49°C).

The valve automatically opens to allow relatively cooler

supply water to refill the pump as the hot water is

discharged to the drain or low pressure return.

The water temperature falls below the opening

temperature by 10º F (5.5°C).

The valve automatically closes in order to conserve water

and reduce waste.