The pump station cycles or hunts erratically – Xylem AquaBoost CS and VS Pumping Packages User Manual

Page 44

Advertising
background image

Cause

Remedy

The diaphragm tank is faulty.

Check for a properly installed diaphragm tank. Has the

tank failed? Has the tank been charged to the proper

operating pressure before installation? (~10 psi below

the desired set point)

The pressure transducers are faulty.

Check the pressure transducers. Does the actual

mechanical gauge pressure match the pressure

displayed on the VFDs and the PLC?

The VFDs are in Local mode.

Put the VFDs in Remote mode.

A check valve is malfunctioning.

Check for malfunctioning check valves. Does the system

hold pressure when the pump package is shut down?

Replace faulty valves.

The pump station cycles or hunts erratically

Cause

Remedy

The pumps are oversized for the current demand.

Check the application. Possibly increase the size of the

bladder tank for low demand situations.

The inlet pressure is fluctuating.

There are leaks or broken pipes.

Check for broken pipes or leaks. Does the system

pressure decrease when the pump station is turned off?

The diaphragm tank is faulty.

Check for a properly installed diaphragm tank. Has the

tank failed? Has the tank been charged to the proper

operating pressure before installation? (~10 psi below

the desired set point)

The pressure transducers are faulty.

Check the pressure transducers. Does the actual

mechanical gauge pressure match the pressure

displayed on the VFDs and the PLC?

A check valve is malfunctioning.

Check for malfunctioning check valves. Replace faulty

valves.

There is an error in the PLC programming.

Check the customer programming on the PLC. Correct

any errors.

Troubleshooting

42