Condition

Description

The lead pump fails.

The lag pump starts and acts as the lead pump.
To reinstate the lead pump do the following:

1. Before fixing the failed pump, turn the HOA

switch to the OFF position.

2. After the lead pump has been fixed, place the

lead pump HOA into the AUTO position and then
press the RESET button to reset the unit.

3. The pump returns to its operational state.

Conditions that cause the unit to cut out

Simplex and duplex units run when there is demand unless one of the following conditions
occurs:

Condition

Description

Resolution

Low city pressure

The optional low-suction pressure

switch (1PS) trips.

The low suction condition resets automatically

when the city pressure returns to an acceptable

level.

Pump deadheading

The high temperature cutout switch

trips.

The unit resets automatically when there is demand

by drawing cooler water through the unit and

across the temperature sensor. This cools the sensor

and causes it to change state and restart the pump.
For a manual purge run the unit in Hand mode for

about 5 seconds. Then put the unit back into Auto

mode for normal operation.

The smart relay control module

The AquaBoost CS duplex pumping package uses a smart relay for its control module. You
can adjust control settings via the front panel of the smart relay.

Commissioning, Startup, Operation, and Shutdown