Pump package operation description, Constant speed operation – Xylem AquaBoost CS and VS Pumping Packages User Manual

Page 34

Advertising
background image

Parameter description

Default setting

(seconds)

Variable range

(seconds)

Field setting

Pump fail to start proof timer

5

0-99

Low suction/high temperature off proof timer

5

0-99

Low suction/high temperature on proof timer

5

0-99

Duty/standby

0

0 = disabled
1 = enabled

Staging on proof timer

30

0-99

For more details on these settings see

Sequence of operation for the duplex pumping

system

(page 36).

Aquastat

The aquastat for high temperature cutout is set at the factory for 100°F (38°C). Adjust the
setting if a different cutout temperature is desired. Do not set the switch above 225°F
(107°C).

Optional tank

A variety of different tanks can be used with either the simplex or duplex units. Refer to the
specific IOM that was shipped with the tank for installation and operating instructions.

Pump package operation description

CAUTION:
A unit that shows symptoms of possible problems, such as overflow, noise, leaks,
vibrations, or continual operation, must be corrected immediately.

Constant speed operation

Constant speed simplex – for capacities up to 110 gpm

Condition

Description

The city water pressure falls below the setting of the

system suction pressure switch (2PS).

The pump starts through a power relay.

The system pressure rises above the setting of the system

pressure switch.

The pump stops, provided the minimum run timer has

expired.

Constant speed duplex – for capacities up to 220 gpm

Condition

Description

The city water pressure falls below the setting of the

system suction pressure switch (2PS).

The lead pump starts through a power relay.

The system pressure rises above the setting of the system

pressure switch.

The lead pump stops, provided the minimum run timer

has expired.

The system demand increases beyond the capacity of the

lead pump and the system pressure does not satisfy the

pressure switch settings.

The system automatically starts the lag pump and both

pumps run.

The system pressure rises above the settings of Pump 1

and Pump 2 discharge pressure switches (2PS and 3PS).

Both pumps stop, provided the minimum run timers

have expired.

Commissioning, Startup, Operation, and Shutdown

32

AquaBoost CS and VS Pumping Packages Installation, Operation, and Maintenance Manual