Xylem HVS 1.1 - 3.4 User Manual

Page 28

Advertising
background image

28

7.4 Submenu Reference Curve

Submenu

Reference Curve

To enter this menu you have to press the Ð

button, to

leave the menu, press the Îbutton longer than 3 sec.

7.4.1 Reference Curve

Reference Curve

0 - 7

Change the curve by pressing Ï

or Ð


This parameter allows selecting different pre programmed curves.


0... Learned curve with 3 up to 12 system-points

1... previous learned system curve

2... Selection A

3... Selection B

4... Selection C

5... Selection D

6... Selection E

7...

Selection

F

7.4.2 Power / Frequency

POWER xxx

FREQ xx.x HZ

Check the learned points by using Ï

and Ð.

(Learned points 1-12)


This parameter allows only the control of the learned points.

7.4.3 Coefficients A / B / C

These coefficients define the actual reference curve 0-7.
To change the coefficients it is necessary to know a special password.
A changing without knowledge about pump curve and power will produce a
malpractice of the pump.

COEFF A / B / C

x.xxx

Change value using Ï

and Ð. Press the Î button

to save and change to next coefficient.

By using reference curve 2...7 it is only necessary to

learn one point at zero flow. You are also able to
change the reference curve while pump is running to
find the best suitable curve.
The different curves depending on the type of pump

and the duty point.