9 Possible Error messages

You have to connect the programming unit to read the error message on the display.

After the cause has been remedied, the malfunction has to be reset by cutting off the

power supply for >30 seconds.

The last 3 error messages are saved in SUBMENU DIAGNOSIS

9.1 Overheating – Motor

XXX

Error-Mot-Temp

Possible causes: insufficient cooling, ambient temperature is too high or motor
overloaded.

9.2 Overvoltage

XXX

Error-Overvolt


Possible causes: Check mains supply, supply voltage too high, peak voltage owing to
switch heavy loads on the network, or RAMP 2 is to fast! Find the cause and take
countermeasures (e.g. network filter, RC-elements).

9.3 Undervoltage

XXX

Error-Undervolt


Possible cause: Check mains supply, faulty fuse or phase unsymmetry.

9.4 Overload

XXX

Error Overload


Possible causes: false data settings or the pump is working at a capacity significantly in
excess of its performance data.
Ramp 1 to fast
Max. frequency to high
Boost to low