2. Technical Data -

Hydrovar sensorless and General Data

HYDROVAR

sensorless

Hydrovar sensorless

output to the Motor

Supply Voltage (U

in

) Prefuse

min.

Type

HVS

Rated

output

Voltage Max.

current

Mains frequency

48-62 [Hz]

[A] Ampere

1.1 1,1

kW

3x0-U

in

4,8 A

1x220-240V ±15%

10

1.15 1,5

kW

3x0-U

in

7,0 A

1x220-240V ±15%

16

1.2 2,2

kW

3x0-U

in

10,0 A

1x220-240V ±15%

20

3.2 2,2

kW

3x0-U

in

5,7 A

3x380-460V ±15%

10

3.3 3

kW

3x0-U

in

7,3 A

3x380-460V ±15%

13

3.4 4

kW

3x0-U

in

9 A

3x380-460V ±15%

16


Output voltage:

3x 0...U

in

VAC / 0-70 Hz

(depends on the input voltage)

Min. frequency:

0 – max. frequency

Electrical efficiency:

> 95%


Protection against: Short circuit, over- and undervoltage, overheating of the

electronics (overload) and additional external protective functions
via PTC (motor temperature) and low water switch.
A mains filter is fitted to ensure interference immunity.


The Hydrovar sensorless complies with the general EMC provisions and has been tested
according to the following standards:

• Disturbance voltage:

EN 55011

• EMC – Immunity:

EN 61000-4-3 and ENV 50204

• Electrostatic discharge:

EN 61000-4-2

Ambient temperature:

5° C ... + 40°C

Storage temperature:

-25° C ... + 55° C
(+70°C during max. 24 hours.)

Humidity:

rH max. 50% at 40°C, unlimited

rH max. 90% at 20°C, max. 30 days per year

Condensation not permitted !

Air pollution:

The air may contain dry dust as found in workshops where
there is no excessive quantity of dust due to machines.
Excessive amounts of dust, acids, corrosive gases, salts etc.
are not permitted

Altitude:

max. 1000m above sea level
At sites over 1000 m above sea level, the maximum output
power is derated by 1% for every additional 100m.
If the installation site is higher than 2000 m above sea level,
please contact your local distributor.

Class of protection:

IP55