7.5 Submenu Test-Run

Submenu

Testrun

To enter this menu you have to press the Ð

button, to

leave the menu, press the Îbutton longer than 3 sec.

7.5.1 Start Test Run

Start Test Run

П

+ Р

By simultaneously pressing П

+ Р a test run will be

released even if the test cycle is not set.

After starting this test run, the pump will speed up with the fasten ramp 1 to the set
speed and then will ramp down with the fasten ramp 2.

7.5.2 Enable Test Run

Enable Test Run

100 h

Adjustable between 1...100 hours.
The test run starts the pump at the set time after

the last stop for 20 seconds with the set speed.
Deactivating test run: Set 0 hours, by using Ï

and Ð.

Repeating the test run: Select the test run and set the desired hours using the Ï

button.

7.5.3 Test Frequency

Test Frequency

30.0 Hz

Frequency for manual and automatic test run.
Can be set from 0 Hz up to 70 Hz.

7.5.4 Boost Test Run

BOOST Test Run

10.0 %.

Start voltage in % of rated voltage in order to ensure
that the motor starts safely.