7.5 Submenu Test-Run
Submenu
Testrun
To enter this menu you have to press the Ð
button, to
leave the menu, press the Îbutton longer than 3 sec.
7.5.1 Start Test Run
Start Test Run
П
+ Р
By simultaneously pressing П
+ Р a test run will be
released even if the test cycle is not set.
After starting this test run, the pump will speed up with the fasten ramp 1 to the set
speed and then will ramp down with the fasten ramp 2.
7.5.2 Enable Test Run
Enable Test Run
100 h
Adjustable between 1...100 hours.
The test run starts the pump at the set time after
the last stop for 20 seconds with the set speed.
Deactivating test run: Set 0 hours, by using Ï
and Ð.
Repeating the test run: Select the test run and set the desired hours using the Ï
button.
7.5.3 Test Frequency
Test Frequency
30.0 Hz
Frequency for manual and automatic test run.
Can be set from 0 Hz up to 70 Hz.
7.5.4 Boost Test Run
BOOST Test Run
10.0 %.
Start voltage in % of rated voltage in order to ensure
that the motor starts safely.