9.5 Overheating of the heat sink
XXX
Error KK-Temp
The thermal sensor, mounted on the cooling body of the HYDROVAR SENSORLESS
indicates over temperature.
Possible causes: insufficient cooling, ambient temperature is too high or motor
overloaded.
9.6 Error Power measurement
XXX
Error Powermeas
No detected signal from the power measurement.
Possible causes: wrong connection on the control card
9.7 Additional internal processor Error messages:
ERROR 1
:
EEPROM-ERROR
(corresponding data block malfunction)
ERROR 2
:
Not used
ERROR 3
:
Processor RAM error
ERROR 4
:
Not used
ERROR 5
:
Processor ROM error
ERROR 6
:
Watchdog error
ERROR 7
:
Timer error (quartz)
ERROR 8
:
Programme error
These ERROR signals are acknowledged by disconnecting the power supply for
> 30 seconds.
If the error signal should appear again, contact customer service and provide a
detailed description of the error.