Xylem HVS 1.1 - 3.4 User Manual

Page 36

Advertising
background image

36

9.5 Overheating of the heat sink

XXX

Error KK-Temp


The thermal sensor, mounted on the cooling body of the HYDROVAR SENSORLESS
indicates over temperature.

Possible causes: insufficient cooling, ambient temperature is too high or motor
overloaded.

9.6 Error Power measurement

XXX

Error Powermeas


No detected signal from the power measurement.

Possible causes: wrong connection on the control card

9.7 Additional internal processor Error messages:

ERROR 1

:

EEPROM-ERROR
(corresponding data block malfunction)

ERROR 2

:

Not used

ERROR 3

:

Processor RAM error

ERROR 4

:

Not used

ERROR 5

:

Processor ROM error

ERROR 6

:

Watchdog error

ERROR 7

:

Timer error (quartz)

ERROR 8

:

Programme error


These ERROR signals are acknowledged by disconnecting the power supply for
> 30 seconds.
If the error signal should appear again, contact customer service and provide a
detailed description of the error.