YSI IQ S ENSOR N ET DIQ/S 182 XT User Manual

Page 126

Advertising
background image

Outputs

System 182

6 - 30

ba76022e01

12/2011

Within the proportional band, a concentration increase by 1 mg/l
causes a decrease of the current output by 1 mA. If, for example, the
measured concentration is 5 mg/l, 11 mA are output:

The highest concentration with which the controller works within the
proportional band is 8 mg/l (corresponding to Imin = 8 mA), the lowest
one is 2 mg/l (corresponding to Imax = 14 mA).

Settings

(

)

mg/l

mg/l

mg/l

mA

1

mA

12

I

Controller

5

4

+

=

(

)

mA

11

mg/l

1

mg/l

mA

1

mA

12

I

Controller

=

+

=

Setting

Selection/Values

Explanation

Measured variable

Main variable
Adjoining variable

Main variable
designates the actual
measured parameter of
the sensor (e.g. pH,
oxygen, etc.).
Adjoining variable
designates an
additional measured
parameter (e.g.
temperature).

Nominal value

within the measuring
range (sensor-
dependent)

Nominal value the
measured value is
regulated to

Xp

5 ... 100 %
-5 ... -100 %
of the measuring
range

Proportional band of
the controller.
Negative values result
in a positive
characteristic curve.

Imin

0 ... 20 mA

Lower current limitation
*

Imax

0 ... 20 mA

Upper current limitation
*

* Note:
Spacing between Imin
and Imax:
at least 5 mA

Advertising