MIQ/CR3; DIQ/CR3

Settings

4 - 7

ba76032e01

01/2012

Pulse width output

The output of the pulse width is used, e.g. for controlling valves.

Pulse-width regulation changes the duration of operation (t

on

) of the

output signal. Depending on the position of the measured value in the
proportional range, the relay is operated for a longer or shorter time
period.

Fig. 4-4

Relay output of the pulse-width output

The cycle duration (T) is made up of the turn-on and turn-off switching
duration (t

on

, t

off

) of the relay together. While the selected cycle

duration (T) remains constant, the turn-on duration (t

on

) changes

depending on the measured value and, with it, the pulse width (v). The
pulse width can be set from 0 % to 100 %.

v = (t

on

/ T) * 100 %

v = pulse width, T = cycle duration, t

on

= turn-on duration

If the measured value is at the end of the proportional range (End
value
), the turn-on duration (t

on

) is long, the turn-off duration is short.

This means the relay operates for a longer period.

If the measured value is at the beginning of the proportional range
(Start value), the turn-on duration (t

on

) is short, and the relay

operates for a correspondingly shorter period.

Note
If the duration of the closing or opening pulse is shorter than 0.1 s, the
relay remains open or closed for the complete cycle duration.

T

Time [s]

Relay

Off

On

t

On

t

Off