6 modbus error elimination, Modbus error elimination -14 – YSI DIQ/S 182-MOD System 182 User Manual
Page 126
Modbus connection
System 182
7 - 14
ba76025e01
02/2012
7.6
Modbus error elimination
Note
Here you will find causes and actions to take of errors concerning the
Modbus communication only. General errors of the IQ S
ENSOR
N
ET
system are dealt with in chapter 9 W
Data transmission
between the Modbus
master and
DIQ/S 182-MOD is faulty
The PLC does not
receive any plausible
input data
Cause
Remedy
– Incorrect wiring of the
Modbus cable on the
connector
– Check/change the connections
(see section 7.2)
– Use checklist according to
– Incorrect setting of address,
baud rate, parity
– Check/change the settings
(see section 7.3)
– Incorrect protocol
– Adapt the protocol
– DIQ/S 182-MOD defective
– Send DIQ/S 182-MOD to YSI
Cause
Remedy
– The data interpretation is not
correct
– Observe data formats of the
DIQ/S 182-MOD (see also
section 7.4.4).