3.3

PROFIBUS / Modbus RTU checklist

The following checklist supports you when planning, projecting and
installing a PROFIBUS or Modbus RTU system with the
IQ S

ENSOR

N

ET

. For smooth operation, you should be able to answer

all questions with "Yes".

Is the [bus system] (bus segment) installed without branch lines?

Was the correct cable used (e.g. PROFIBUS cable, see section
2.1)
?

Are the poles of the signal lines A line and B line correctly connected
at all bus connections?

Is it guaranteed that there is no short-circuit between A line, B line
and cable shielding?

Is the shielding installed free of interruptions?

Are the guidelines for shielding and grounding being observed, and
doesn't any unallowed potential equalization current flow via the
shielding?

Is the maximum cable length (per bus segment) observed for the
corresponding baud rate?

Do all devices support the required baud rate?

Only for Profibus:
With 12 Mbit/s transmission rate only: Are the bus plugs suitable for
this baud rate?

Are exactly two terminators switched on at the ends of the [bus sys-
tem] (bus segment)?

Are the terminators supplied with voltage so the following applies:
U

B line

- U

A line

> + 500 mV?

Do all devices have individual bus addresses?

After changing the bus address, have the devices been restarted
(switched off and on again)?
Note: The IQ S

ENSOR

N

ET

does not have to be restarted.

Do the addresses projected in the master correspond to the actual
addresses?
Are all addresses less than or equal to the parameter
HSA and less than 126 (HSA = Highest Station Address)?

Only for Profibus:
Is the currently valid GSD being used? If you are in doubt, download
it from the Internet.

Only for Profibus:
Have admissible bus parameters been set only? If you are in doubt
set them to default values.