YSI IQ S ENSOR N ET Field bus linking User Manual

Page 30

Advertising
background image

Communication with field buses

IQ S

ENSOR

N

ET

Field bus linking

28

ba76148e01

06/2013

Response with sensor

data block of the

sensors S02

Modbus response

Byte Value

Information

Meaning of the value

1

01h

Modbus address of the
IQ S

ENSOR

N

ET

01h --> 1

2

04h

Function

04h --> 4
Read Input Register

3

10h

Number of bytes

10h --> 16
16 Byte (8 registers)

4

02h

Contents of register 9 (HI)
= sensor number

02h (Int 8) --> 2
Sensor number S02

5

02h

Contents of register 9 (LO)
= sensor status

02h (Int 8) -->
MEASURE
see section 5.2

6

04h

Contents of register 10 (HI)
= sensor model

0401h (Int 16)
--> VisoTurb 700 IQ
see section 5.3

7

01h

Contents of register 10 (LO)
= sensor model

8

00h

Contents of register 11 (HI)
= status info

0000h (Int 16)
--> no errors
see section 5.4

9

00h

Contents of register 11 (LO)
= status info

10

00h

Contents of register 12 (HI)
= measuring mode

00h (Int 8) --> FNU
Turb
see section 5.5

11

14h

Contents of register 12 (LO)
= measured value status

14h (Int 8)
Main measured value
(bits 7-4):
1h --> VALID
Secondary measured
value (bits 3-0):
4h --> MISSING
see section 5.6

Advertising