4.1.3 Data block of the sensors (input data of the PLC)

16 bytes - from the IQ S

ENSOR

N

ET

to the superordinate control system

(PLC)
For Ethernet IP: Instance ID =102 (SensorData)

Address

Information

Data format

Data
type

Bit

Offset 0h

Sensor number

Int 8

7-0

Offset 1h

Sensor status

Int 8

7-0

Offset 2h

Sensor model

Int 16

15-8

Offset 3h

7-0

Offset 4h

Status info

Int 16

15-8

Offset 5h

7-0

Offset 6h

Measuring mode

Int 8

7-0

Offset 7h

Status of main measured value

Int 8

7-4

Status of secondary measured value

3-0

Offset 8h

Main measured value (IEEE-754 floating point,
32-bit)

Float 32

31-24

Offset 9h

23-16

Offset Ah

16-8

Offset Bh

7-0

Offset Ch

Secondary measured value (IEEE-754 floating point,
32-bit)

Float 32

31-24

Offset Dh

23-16

Offset Eh

16-8

Offset Fh

7-0