Interface for the Modbus RTU

MIQ/(A-)MOD

12

ba76021e01

01/2012

3.2.2

Connecting the Modbus cable

The MIQ/(A-)MOD component can be connected at the Modbus end
(A) or with a loop-through (B).

An RS 485 point-to-point connection has to be installed as a
component at the end of the Modbus (A).

Fig. 3-4

Connection options of the MIQ/(A-)MOD at the Modbus cable,
(A) at the end or (B) with loop-through

Note
All cables with electrical characteristics according to EN 50170 are
suitable as a Modbus cable (e.g. all Profibus cables).

(A)

Connecting the

MIQ/(A-)MOD

component

at the Modbus end

Fig. 3-5

Modbus cable with insulating tape

(A)

(B)

(A)

instrument connected
at the Modbus,
e.g. MIQ/(A-)MOD

Modbus cable

1

Carefully strip the Modbus cable insulation for approx. 20 mm.

2

Bare the Modbus wires from the shielding braid and strip them
for approx. 5 mm.

3

Twist the shielding braid and cover it with approx. 15 mm
insulating tube.

4

Insert the Modbus cable into the module housing of the MIQ/
MC(-A)-MOD through the screwed cable gland.

5

Additionally insulate the transition between cable sheath and
insulating tube of the shielding braid (e.g. with insulating tape
or shrinkable tubing), so that no shielding braid is uncovered.