5 what to do if, 1 fault diagnosis, 2 error elimination – YSI IQ SensorNet MIQ/A-MOD Module User Manual

Page 35: What to do if, Fault diagnosis, Error elimination, Chapter 5 w, S (see chapter 5 w, 5what to do if

Advertising
background image

MIQ/(A-)MOD

What to do if ...

35

ba76021e01

01/2012

5

What to do if ...

5.1

Fault diagnosis

A simple diagnosis of the operability of the Modbus module and
communication with the Modbus is possible via the LEDs on the
Modbus module in the MIQ/MC (-A)-MOD (see section 3.2.4).

5.2

Error elimination

Data transmission

between the Modbus

master and

IQ S

ENSOR

N

ET

system is

faulty

The Modbus master

does not receive any

plausible input data

Cause

Remedy

– Incorrect wiring of the

connections on the terminal
strip

– Check/change the connections

on the terminal strip (see
section 3.2.1)

– Incorrect setting of address,

baud rate, parity

– Check/change the settings

(see section 3.2.3)

– Incorrect protocol

– Adapt the protocol

– Modbus module defective

– Send MIQ/MC(-A)-MOD

module to YSI

Cause

Remedy

– The data interpretation is not

correct

– Observe data formats of the

MIQ/MC(-A)-MOD (see also
section 4.5).