4 modbus checklist, Modbus checklist – YSI IQ SensorNet MIQ/A-MOD Module User Manual

Page 21

Advertising
background image

MIQ/(A-)MOD

Interface for the Modbus RTU

21

ba76021e01

01/2012

3.4

Modbus checklist

The following checklist supports you when planning, projecting and
installing a Modbus plant with the IQ S

ENSOR

N

ET

. For smooth

operation, you should be able to answer all questions with "Yes".

 Is the [bus system] (bus segment) installed without branch lines?

 Was the correct Modbus cable used (cord type A according to

EN 50170)?

 Are the poles of the signal lines A line and B line correctly connected

at all bus connections?

 Is it guaranteed that there is no short-circuit between A line, B line

and cable shielding?

 Is the shielding installed free of interruptions?

 Are the guidelines for shielding and grounding being observed, and

doesn't any unallowed potential equalization current flow
via the shielding?

 Is the maximum cable length (per bus segment) observed for the

corresponding baud rate?

 Do all devices support the required baud rate?

 Are exactly two terminators switched on at the ends of the [bus

system] (bus segment)?

 Are the terminators supplied with voltage so the following applies:

U

B line

- U

A line

> + 500 mV?

 Do all devices have individual bus addresses?

 Have the devices been restarted after changing the bus address,

baud rate or parity (switched off and then on again)?

 Do the addresses projected in the master correspond to the actual

addresses?

 After commissioning:

Do all devices signal error-free behavior?

 Is it guaranteed that the Modbus master has consistent access

to the 16 byte sensor data structure?