YSI IQ SensorNet MIQ/A-MOD Module User Manual

Page 14

Advertising
background image

Interface for the Modbus RTU

MIQ/(A-)MOD

14

ba76021e01

01/2012

(B)

Connecting the

MIQ/(A-)MOD

component at the

Modbus with a loop-

through

To loop the Modbus cable through the MIQ/(A-)MOD component, a
shielding terminal is included in the scope of delivery.

Fig. 3-7

Shielding terminal with Modbus cable and shield connection cable

1

Screw

2

Washer

3

Insulating part of the shielding
terminal

4

Cable insulation of the Modbus cable

5

Shielding braid of the Modbus cable

6

Wires of the Modbus cable

7

Shield connection wire

1

Carefully strip the cable insulation of both Modbus cables for
approx. 35 mm.

2

Shorten the exposed shielding braid to approx. 15 mm.

3

Bare the Modbus wires for approx. 5 mm.

4

Feed both cables through the free cable glands into the
module housing of the MIQ/(A-)MOD.

5

Create a shield connection wire (7). To do so, strip a wire on
both ends for approx. 5 mm and 10 mm.

6

Insert a washer in the insulating part (3) of the shielding
terminal.

7

Feed both Modbus cables into the insulating part (3) and lead
them through the insulating part.

1

2

5

7

4

3

6