4 bus and module monitoring, Bus and module monitoring – YSI IQ SensorNet MIQ/A-MOD Module User Manual
Page 18

Interface for the Modbus RTU
MIQ/(A-)MOD
18
ba76021e01
01/2012
3.2.4
Bus and module monitoring
The Modbus module has 4 LEDs for monitoring the bus and one LED
for monitoring the Modbus module. These 5 LEDs are important aids
for the monitoring and diagnosis of faults.
Bus monitoring
The LEDs have the following meaning:
Fig. 3-11 LEDs for bus monitoring
LED Color
Meaning
1
Flashes
green
Data exchange
(the module receives or transmits data.)
Off
No data exchange
2
Red
Bus error
(more than 10% of the received telegrams have
wrong CRC values.)
Off
The module is operating or not initialized
3
Green
Modbus is ready for operation
Off
The module is not correctly initialized
4
Red
The dip switches are set to invalid values
(all dip switches are set to Off or
to invalid values.)
Off
The dip switches are set to valid values
4
1
2
3