MIQ/(A-)MOD
Interface for the Modbus RTU
15
ba76021e01
01/2012
Fig. 3-8
Shielding terminal with Modbus cable (view from above)
Fig. 3-9
Looping the Modbus cable through an MIQ/(A-)MOD
8
Feed the long stripped end of the shield connection wire (7)
into the insulating part (3) of the shielding terminal.
9
Position the second washer and screw it tight.
10
Shorten the wires of the shielding braid if they protrude over
the shielding terminal.
11
Put the Modbus wires together in pairs.
12
Connect the Modbus wires and shield to the terminal
connections of the Modbus module (connections ALine, BLine
and Shield, see section 3.2.1).
approx.
15 mm
approx.
15 mm
approx.
5 mm
4
2
6
7
1
3
AnyBus-S
Modbus RTU