YSI IQ SensorNet MIQ/A-MOD Module User Manual

Page 17

Advertising
background image

MIQ/(A-)MOD

Interface for the Modbus RTU

17

ba76021e01

01/2012

Address

A prerequisite for the configuration of the AnyBus-S Modbus RTU
Modbus module is the setting of its address. The setting of the address
is carried out with the dip switches, 1-7 (1). Each switch sets the value
0 or 1 for one digit of the seven-digit binary number. This enables
addresses of 0-127 to be set.

Examples:

Baud rate

A prerequisite for the configuration of the AnyBus-S Modbus RTU
Modbus module is the setting of the baud rate. The setting of the baud
rate is carried out with the dip switches, 8,1,2 (2). Each switch sets the
value 0 or 1 for one digit of the three-digit binary number. This makes
seven valid settings possible.

Parity

A prerequisite for the configuration of the AnyBus-S Modbus RTU
Modbus module is the setting of the parity. The setting of the parity is
carried out with the parity dip switches, 3,4 (3). Each switch sets the
value 0 or 1 for one digit of the two-digit binary number. This makes
three valid settings possible.

Address

Setting on S1, dip switches 1-7

invalid

0000000

1

0000001

30

0011110

127

1111111

Baud rate

Setting on S1, dip switch 8
and S2, dip switches 1-2

invalid

000

1200

001

2400

010

4800

011

9600

100

19200

101

38400

110

57600

111

Parity

Setting on S2, dip switches 3-4

invalid

00

None (2 stop bits)

01

Even (1 stop bit)

10

Odd (1 stop bit)

11