Interface for the Modbus RTU

MIQ/(A-)MOD

18

ba76021e01

01/2012

3.2.4

Bus and module monitoring

The Modbus module has 4 LEDs for monitoring the bus and one LED
for monitoring the Modbus module. These 5 LEDs are important aids
for the monitoring and diagnosis of faults.

Bus monitoring

The LEDs have the following meaning:

Fig. 3-11 LEDs for bus monitoring

LED Color

Meaning

1

Flashes
green

Data exchange
(the module receives or transmits data.)

Off

No data exchange

2

Red

Bus error
(more than 10% of the received telegrams have
wrong CRC values.)

Off

The module is operating or not initialized

3

Green

Modbus is ready for operation

Off

The module is not correctly initialized

4

Red

The dip switches are set to invalid values
(all dip switches are set to Off or
to invalid values.)

Off

The dip switches are set to valid values

4

1

2

3