4 data transmission, 1 overview, 2 modbus query – YSI IQ SensorNet MIQ/A-MOD Module User Manual

Page 25: Data transmission, Overview, Modbus query, 4data transmission

Advertising
background image

MIQ/(A-)MOD

Data transmission

25

ba76021e01

01/2012

4

Data transmission

4.1

Overview

Data transmission is carried out via the RS 485 interface with the
Modbus RTU protocol.

The following sensor data is transmitted:

 Sensor number (Sxx)

 Sensor status

 Sensor model

 Status info of sensors

 Measuring mode

 Measured value status (main and secondary measured value)

 Main measured value

 Secondary measured value

Note
The transmitted data of all IQ S

ENSOR

N

ET

sensors is given in the YSI

document, "IQ S

ENSOR

N

ET

sensors: encoded data for field bus

communication" (ba76073e). It is permanently updated when new
sensors are available and when the sensor software is modified (if the
modifications are relevant for the transmitted sensor data). The latest
version is available on the Internet, in the download area for operating
manuals. Use the search function for the download and search for
"ba76073e".

4.2

Modbus query

With each query of sensor data via the Modbus protocol, a block of
consecutive registers is read (up to all of the 240 registers).
For a query of sensor data, determine the first register and the number
of registers to be read (1 ... 240).

Determining the first

register to be read

The first register to be read depends on the sensor number (Sxx) [1 ...
30] and the number of the sensor register (R) [1 ... 8]:

[(Sxx - 1)] * 8 + R.

Example: Determine the first register with data for the sensor S10:
[(10 - 1) * 8] + 1 = 73